Micro MotionTMModel 3500 Transmitter(9-wire) or Model 3300 PeripheralInstallation Instructions forRack-MountQuick Reference GuideP/N 3300995, Rev. CAp
95. At the transmitter:a. Connect the color-coded wires to the appropriate terminals. To identify the terminals, refer to Figure 5, page 8. No bare wi
10Figure 6. Power supply wiring terminalsPower supply wiringterminalsTerminal designations for AC powerTerminal designations for DC power
Micro MotionTMMicro Motion EuropeEmerson Process ManagementWiltonstraat 303905 KW VeenendaalThe NetherlandsT +31 (0) 318 495 670F +31 (0) 318 495 689M
1BEFORE YOU BEGINThis quick reference guide explains basic installation guidelines for mounting the Micro Motion® Model 3300/3500 applications platfor
2European installationsThis Micro Motion product complies with all applicable European directives when properly installed in accordance with the instr
3Figure 1. Space requirements for proper ventilationDimensionsThe Model 3300/3500 has the following dimensions (see Figure 2, page 4):• Height: 128 mm
4Figure 2. Dimensions for mounting in rackFlowmeter cable lengthsMaximum cable length from the sensor to the Model 3500 transmitter is 1000 feet (300
5STEP 2. Installing guide rails and wiring connectorsGuide railsPositions of guide rails and wiring connectors are indicated in Figure 3, page 6. Cent
6Figure 3. Positions of guide rails and wiring connectorsSTEP 3. Installing the Model 3300/3500 in the rack1. Align the Model 3300/3500 with the guide
7STEP 4. Connecting input and output wiringConnect input and output wiring to the appropriate terminals on the input/output wiring connector, which is
81. Identify the components shown in Figure 5.Figure 5. Sensor cable to Model 35002. Prepare the cable according to the instructions in Micro Motion’s